XSCF> replacefru (M9000更换大部分硬件通用)
----------------------------------------------------------------------
Maintenance/Replacement Menu
Please select a type of FRU to be replaced.
1. CMU/IOU (CPU Memory Board Unit/IO Unit)
2. FAN (Fan Unit)
3. PSU (Power Supply Unit)
4. XSCFU (Extended System Control Facility Unit)
----------------------------------------------------------------------
Select [1-4|c:cancel] :1 (按照日志中故障备件选对应故障硬件编号)
----------------------------------------------------------------------
Maintenance/Replacement Menu
Please select whether to replace a CMU only, an IOU only,
or both a CMU and an IOU.
1. Replace CMU only.
2. Replace IOU only.
3. Replace both CMU and IOU.
----------------------------------------------------------------------
Select [1-3|b:back] :2 (按照日志中故障备件选对应故障硬件编号)
----------------------------------------------------------------------
Maintenance/Replacement Menu
Please select an IOU to be replaced.
DomainID
No. FRU XSB#0 XSB#1 XSB#2 XSB#3 Power Status
--- ------------- ----------------------- ----- ---------------
1. IOU#0 0 0 0 0 On Normal
2. IOU#1 1 1 1 1 Off Normal
3. IOU#2 0 0 0 0 On Not installed
4. IOU#3 0 0 0 0 On Not installed
5. IOU#4 0 0 0 0 On Normal
6. IOU#5 1 1 1 1 Off Degraded
7. IOU#6 3 3 3 3 On Not installed
8. IOU#7 3 3 3 3 On Normal
9. IOU#8 4 4 4 4 On Normal
10. IOU#9 4 4 4 4 On Not installed
11. IOU#10 5 5 5 5 On Normal
12. IOU#11 5 5 5 5 On Not installed
13. IOU#12 -- -- -- -- --- Not installed
14. IOU#13 -- -- -- -- --- Not installed
15. IOU#14 -- -- -- -- --- Not installed
--More-- (89% of 1316 bytes) 16. IOU#15 -- -- -- -- --- Not installed
--More-- (94% of 1316 bytes) ----------------------------------------------------------------------
Select [1-16|b:back] :6 (输入当前故障IOU板卡位置对应的编号)
----------------------------------------------------------------------
Maintenance/Replacement Menu
Status of the selected FRU.
FRU Status
------------- --------
IOU#5 Degraded
----------------------------------------------------------------------
You are about to replace IOU#5.
Do you want to continue?[r:replace|c:cancel] :r (点击更换 停止更换选停止)
Please confirm the Ready LED is not lit and that the Check LED is
blinking.
If this is the case, please replace IOU#5. (按照提示拔出故障IOU板卡)
After replacement has been completed, please select[f:finish] :f
To ensure correct operation, diagnostic tests should be run on
IOU#5.[d:diagnose|s:skip] :d (更换成功后进行测试点击D 跳过测试点击S)
Diagnostic tests for IOU#5 have started.
[This operation may take up to 60 minute(s)]
(progress scale reported in seconds)
0..... 30..... 60..... 90..... 120..... 150..... 180..... 210.....
240..done
----------------------------------------------------------------------
Maintenance/Replacement Menu
Status of the selected FRU.
FRU Status
------------- --------
IOU#5 Normal
----------------------------------------------------------------------
The replacement of IOU#5 has completed normally.[f:finish] :f (点击完成)
----------------------------------------------------------------------
Maintenance/Replacement Menu
Please select a type of FRU to be replaced.
1. CMU/IOU (CPU Memory Board Unit/IO Unit)
2. FAN (Fan Unit)
3. PSU (Power Supply Unit)
4. XSCFU (Extended System Control Facility Unit)
----------------------------------------------------------------------
Select [1-4|c:cancel] :c (点击退出)